Reviewed configuration

NHS-6/1 DC disconnect combiner

A 1000V DC configuration with 6 input and 1 output boundary. Confirm the project specification before release.

NHS-6/1 DC disconnect combiner

Source-backed technical data

Complete configuration parameters, not only a model summary.

The table below is transcribed from the approved catalogue technical sheet for this configuration. The final drawing, BOM and inspection scope remain subject to the agreed project specification.

Configuration summary

ModelNHS-6/1
Configuration typeDC disconnect combiner
Voltage class1000V DC
Input count6
Output count1
Protection / switching architectureload-break disconnect

Technical specifications

Input6 strings
Output1 string
Maximum Voltage1000V
Max DC Short Circuit Current Per Input (Isc)15A (Changeable)
Maximum Current Output80A
Material TypePolycarbonate/ABS
Degree of ProtectionIP65
Degree of Resistance to ImpactsIK10
Dimension (WxHxD)540 x 360 x 180mm
Cable Input EntryPG09 Cable Gland, 2.5-16mm²
Output Cable GlandPG36 50-70mm²
DC Switch DisconnectorBH-250
Rated Insulation Voltage (Ui)1000V
Rated Current (Ie)125A
Standard Compliance with (DC Switch)IEC 60947-3
Certification (DC Switch)CB, CE
DC Surge ArresterBUD-40/3
Max Operation Voltage (Ucpv)1000V
Standard Compliance with (SPD)EN 50539 Type 2
Maximum Discharge Current40 KA
Certification (SPD)TUV CE
DC fuse holderBR-30
LED IndicatorYes
Rated Working Voltage (fuse holder)1000V
Fuse Link10x38mm LITTEL 15A
Certification (fuse holder)UL, CB, CE
Operating Temperature-20°C~+60°C
Humidity99%
Altitude2000M
InstallationWall Mounting