Configuration summary
| Model | NBWX-6 |
|---|---|
| Configuration type | AC combiner box |
| Voltage class | 800V AC |
| Input count | 6 |
| Output count | 1 |
| Protection / switching architecture | MCCB + Type 2 AC SPD |
Technical specifications
| Grid topology | TN-S (5-conductor system: L1, L2, L3, PE, N) |
|---|---|
| Rated Voltage (UN) | 800V |
| Rated Insulation Voltage (Ui) | 1000V |
| Frequency | 50Hz/60Hz |
| Operating Temperature | -25 °C up to +60 °C |
| Enclosure | Up to IP65 (IEC 60529) / IK 10 (IEC62262) |
| Material | Powder Coating Metal |
| Dimension | 194*100*40cm |
Ac Input
| Number (Inverter) | 6 *up to 100KW solar inverters | 6 *up to 120KW solar inverters | 6 *up to 160KW solar inverters |
|---|---|
| AC Breaker | 6*800V 160A | 6*800V 200A | 6*800V 250A |
| Rated Current per Input (Inc) | Up to 160A | Up to 200A | Up to 250A |
| Connection | Via V-clamp (for Al and Cu cables) |
Ac Output
| Number | 1 per phase (Optionnally 2) |
|---|---|
| AC Breaker | 1*800V 1000A | 1*800V 1250A | 1*800V 1600A |
| Rated Current Output(InA) | 1000A | 1250A | 1600A |
| Connection/Via | V-clamp (for Al and Cu cables) |
Surge Protection Device
| Type | Type 2AC 4P |
|---|
Technical context
Use the relevant selection guide before finalizing the scope.
Solar PV / Application guide
PV AC Combiner Box: A Practical Guide to Functions, Sizing, and Installation
How does a PV AC combiner box work? Learn its functions, breaker sizing rules, and installation steps — then request a quote from NEUTRON.
Read Insight →Solar PV / Application guideComparing AC and DC Combiner Boxes: A Complete Guide for Solar Installers
AC and DC combiner boxes occupy opposite sides of the inverter. This guide compares their topology, protection, voltage duty and selection basis for solar projects.
Read Insight →